Wire Gauge / Voltage Drop

Size a DC wire for a voltage-drop target.

Live results

Minimum gauge for voltage drop only
20 AWG
Conductor cross-section
0.51762 mm²

Adjust the circuit

Supply voltage
Load current
One-way wire length
Allowable voltage drop

At the far end of the cable

5 VSupply4.8668 VAt load

2.6647% lost over the loop · 0.13323 W

20 AWG0.51762 mm²

Conductor view is scaled for comparison. Voltage-drop sizing only.

All calculated values

Live results

Minimum gauge for voltage drop only
20 AWG
Conductor cross-section
0.51762 mm²
Loop voltage drop
0.13323 V
Voltage drop
2.6647 %
Cable power loss
0.13323 W
Formula and assumptionsRloop = ρ × 2L / A · ΔV = I × Rloop · Ploss = I²Rloop

Low-voltage DC, one-way length with an equal return conductor, solid-equivalent AWG 40–0, at 20°C. Copper ρ=0.017241; aluminum ρ=0.028264 Ω·mm²/m. Smallest area meeting voltage drop only—not a safe ampacity recommendation. Check insulation, temperature, bundling, terminals and applicable wiring rules separately. Not for mains or building wiring.